§ 49.4176 VOC emissions control requirements for covers and closed-vent systems.
(a) Applicability. The VOC emissions control requirements in this section apply to each cover on a storage vessel that is subject to § 49.4173, and to each closed-vent system that is used to convey VOC emissions from the collection of all storage vessels, glycol dehydration units, or pneumatic pumps (to a vapor recovery system or control device) that are subject to §§ 49.4173 through 49.4175.
(b) Exemptions. This section does not apply to covers and closed-vent systems that are subject to the requirements for covers and closed-vent systems in 40 CFR part 60, subparts OOOO or OOOOa, or 40 CFR part 63, subpart HH.
(c) Covers. Each owner or operator must equip all openings on each storage vessel with a cover to ensure that all flashing, working, standing and breathing loss emissions are routed through a closed-vent system to a vapor recovery system, an enclosed combustor, or a flare.
(1) Each cover and all openings on the cover (e.g., access hatches, sampling ports, pressure relief valves (PRV), and gauge wells) must form a continuous impermeable barrier over the entire surface area of the crude oil, condensate, intermediate hydrocarbon liquids, or produced water in the storage vessel.