§ 60.4355 How do I establish and document a proper parameter monitoring plan?
(a) The steam or water to fuel ratio or other parameters that are continuously monitored as described in §§ 60.4335 and 60.4340 must be monitored during the performance test required under § 60.8, to establish acceptable values and ranges. You may supplement the performance test data with engineering analyses, design specifications, manufacturer's recommendations and other relevant information to define the acceptable parametric ranges more precisely. You must develop and keep on-site a parameter monitoring plan which explains the procedures used to document proper operation of the NOX emission controls. The plan must:
(1) Include the indicators to be monitored and show there is a significant relationship to emissions and proper operation of the NOX emission controls,
(2) Pick ranges (or designated conditions) of the indicators, or describe the process by which such range (or designated condition) will be established,